YHAKXS 1*185/50 12/20KV

Description

Description

Standards

  • Product
    IEC 60502-2
  • Test
    IEC 60332-1-2

12/20 KV AL/SC/XLPE/SC/SC TAPE/CU WIRES/ low temp. PVC

 

APPLICATION

Power use outdoor application, even wet.

Suitable for fixed installations at open air, in tube or canals and underground.

Max. Operation temperature: 90°

Max. Short circuit temperature : 250° (Max 5 s)

 

 

 

CONSTRUCTION

1. Conductor:

Compacted Round conductor class 2

2. Insulation:

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer + Semi-conductive tape

3. Metallic screen layer:

Copper wires with open helix copper tape

4. Outer sheath:

Low Temperature PVC, Red or as per customer requirement

5. Marking:

By Inkjet

6. Packing:

Drums can be wooden or steel

 

 

 

 

 

TEST AT WORKS / PRÓBY FABRYCZNE

Routine Tests / Badania rutynowe:

• Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.2 / Maks. rezystancja DC żył w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-2 pkt 16.2

• High voltage test acc. to IEC 60502-2 parag. 16.4 / Próba wysokim napięciem zgodnie z IEC 60502-2 pkt 16.4

• Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.3 / Badanie maksymalnych wyładowań niezupełnych przy 1,73 Uo zgodnie z IEC 60502-2 pkt 16.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided  / Firma Liban Cables przeprowadzi te badania dla wszystkich odcinków kabli i dostarczy świadectwa z badań

 

Sample tests / Badania próbek:

• Check of the build - up and color coding of the cable / Sprawdzenie rozwijania i kolorowych oznaczeń kabla

• Check of dimensions / Sprawdzenie wymiarów

Insulation / Izolacja        :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.      17.5.2

Metallic screen / Ekran metaliczny          :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.7

Oversheath / Powłoka zewnętrzna           :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10 /-Badanie stopnia usieciowania izolacji z XLPE zgodnie z IEC 60502-2 pkt 17.10

 

These tests will be carried out on one length of each size during each inspection . / Badania te – podczas każdej kontroli – zostaną przeprowadzone na jednym odcinku dla każdego rozmiaru kabla.

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

 

Type tests / Próby typu

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2. / Charakterystyki mechaniczne materiałów izolacji i powłoki zewnętrznej (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z IEC 60502-2.

These tests will be carried out on one length of the order / Badania te zostaną przeprowadzone na jednym odcinku z zamówienia

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

DRAWING YnHAKXS

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor flexibility
Stranded class 2
Conductor shape
Circular compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Concentric conductor
Copper wires and helical copper tape
Outer sheath
PVC
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
185 mm²
Conductor diameter
16.2 mm
Nominal insulation thickness
5.5 mm
Screen section
50 mm²
Nominal outer sheath thickness
2.1 mm
Nominal outer diameter
35.0 mm
Approximate net weight
1673 kg/km

Electrical characteristics

Electrical characteristics

Test voltage
42 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Frequence
50 Hz
Perm current rating in air 30°C
424 A
Permissible current rating when buried
317 A
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.21 Ohm/km
Permissible short circuit current conductor 1s
17.8 kA
Thermal soil resistivity wet zone
1.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

U.V resistance
Yes
Flame retardant
IEC 60332-1-2
Bending factor when laying
20 (xD)
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Minimum operating temperature
-35 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000054-LBNI
  • Certification Date : 5/20/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 4
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close